The RPF-AA/AB Series Electronic Expansion Valve is designed for precise refrigerant flow control in refrigeration, air-conditioning, and heat pump systems. It automatically adjusts refrigerant flow to maintain optimal system performance, ensuring stable temperature control, improved energy efficiency, and reliable operation. With its compact design, fast response, and low-noise performance, it is suitable for modern HVAC and cooling applications.
Refrigeration Capacity Extension Sheet (R22)
| Product Model | Condensing Temperature CT (°C) |
Cooling Capacity [kW] Evaporating Temperature [°C] |
|||||
|---|---|---|---|---|---|---|---|
| -40 | -30 | -20 | -10 | 0 | 10 | ||
| RPF(AA)1.0 | 25 | 2.8 | 2.8 | 2.7 | 2.6 | 2.4 | 2.0 |
| RPF(AA)1.3 | 5.6 | 5.6 | 5.4 | 5.2 | 4.7 | 3.9 | |
| RPF(AA)1.6 | 9.4 | 9.3 | 9.1 | 8.7 | 7.9 | 6.6 | |
| RPF(AA)1.8 | 11.1 | 11.1 | 10.9 | 10.3 | 9.4 | 7.8 | |
| RPF(AA)2.0 | 13.8 | 13.7 | 13.4 | 12.8 | 11.6 | 9.7 | |
| RPF(AA)2.2 | 14.8 | 14.7 | 14.4 | 13.7 | 12.5 | 10.4 | |
| RPF(AA)2.4 | 17.4 | 17.4 | 17.0 | 16.2 | 14.7 | 12.3 | |
| RPF(AA)3.0 | 28.9 | 28.8 | 28.1 | 26.8 | 24.4 | 20.3 | |
| RPF(AA)3.2 | 31.8 | 31.7 | 31.0 | 29.5 | 26.9 | 22.3 | |
| RPF(AB)4.0 | 52.9 | 52.7 | 51.6 | 49.1 | 44.7 | 37.2 | |
| RPF(AB)4.5 | 70.8 | 70.5 | 69.0 | 65.7 | 59.8 | 49.7 | |
| RPF(AA)1.0 | 35 | 2.9 | 2.9 | 2.9 | 2.8 | 2.7 | 2.4 |
| RPF(AA)1.3 | 5.8 | 5.8 | 5.8 | 5.7 | 5.4 | 4.9 | |
| RPF(AA)1.6 | 9.8 | 9.8 | 9.8 | 9.5 | 9.0 | 8.2 | |
| RPF(AA)1.8 | 11.6 | 11.7 | 11.6 | 11.3 | 10.7 | 9.7 | |
| RPF(AA)2.0 | 14.4 | 14.5 | 14.4 | 14.0 | 13.3 | 12.0 | |
| RPF(AA)2.2 | 15.4 | 15.5 | 15.4 | 15.0 | 14.3 | 12.9 | |
| RPF(AA)2.4 | 18.2 | 18.3 | 18.2 | 17.7 | 16.8 | 15.2 | |
| RPF(AA)3.0 | 30.1 | 30.3 | 30.1 | 29.3 | 27.8 | 25.2 | |
| RPF(AA)3.2 | 33.1 | 33.4 | 33.2 | 32.3 | 30.7 | 27.8 | |
| RPF(AB)4.0 | 55.1 | 55.5 | 55.2 | 53.8 | 51.0 | 46.2 | |
| RPF(AB)4.5 | 73.8 | 74.3 | 73.8 | 72.0 | 68.2 | 61.8 | |
| RPF(AA)1.0 | 45 | 2.9 | 3.0 | 3.0 | 3.0 | 2.9 | 2.7 |
| RPF(AA)1.3 | 5.9 | 6.0 | 6.0 | 6.0 | 5.8 | 5.5 | |
| RPF(AA)1.6 | 9.9 | 10.1 | 10.1 | 10.0 | 9.8 | 9.2 | |
| RPF(AA)1.8 | 11.8 | 12.0 | 12.0 | 11.9 | 11.6 | 10.9 | |
| RPF(AA)2.0 | 14.6 | 14.8 | 14.9 | 14.7 | 14.3 | 13.5 | |
| RPF(AA)2.2 | 15.7 | 15.9 | 16.0 | 15.8 | 15.4 | 14.5 | |
| RPF(AA)2.4 | 18.5 | 18.8 | 18.8 | 18.7 | 18.1 | 17.1 | |
| RPF(AA)3.0 | 30.5 | 31.0 | 31.2 | 30.9 | 30.0 | 28.3 | |
| RPF(AA)3.2 | 33.7 | 34.2 | 34.4 | 34.0 | 33.1 | 31.2 | |
| RPF(AB)4.0 | 56.0 | 56.9 | 57.2 | 56.6 | 55.0 | 52.0 | |
| RPF(AB)4.5 | 74.9 | 76.1 | 76.5 | 75.8 | 73.6 | 69.5 | |
| RPF(AA)1.0 | 55 | 2.9 | 3.0 | 3.0 | 3.0 | 3.0 | 2.9 |
| RPF(AA)1.3 | 5.8 | 6.0 | 6.0 | 6.1 | 6.0 | 5.8 | |
| RPF(AA)1.6 | 9.8 | 10.0 | 10.2 | 10.2 | 10.1 | 9.8 | |
| RPF(AA)1.8 | 11.6 | 11.9 | 12.1 | 12.1 | 12.0 | 11.6 | |
| RPF(AA)2.0 | 14.4 | 14.7 | 14.9 | 15.0 | 14.8 | 14.3 | |
| RPF(AA)2.2 | 15.5 | 15.8 | 16.1 | 16.1 | 15.9 | 15.4 | |
| RPF(AA)2.4 | 18.2 | 18.7 | 18.9 | 19.0 | 18.8 | 18.2 | |
| RPF(AA)3.0 | 30.1 | 30.9 | 31.3 | 31.4 | 31.0 | 30.1 | |
| RPF(AA)3.2 | 33.2 | 34.0 | 34.5 | 34.6 | 34.2 | 33.1 | |
| RPF(AB)4.0 | 55.3 | 56.6 | 57.4 | 57.6 | 56.9 | 55.1 | |
| RPF(AB)4.5 | 73.9 | 75.7 | 76.8 | 77.0 | 76.1 | 73.7 | |
Refrigeration Capacity Extension Sheet (R407C)
| Product Model | Condensing Temperature CT (°C) |
Cooling Capacity [kW] Evaporating Temperature [°C] |
|||||
|---|---|---|---|---|---|---|---|
| -40 | -30 | -20 | -10 | 0 | 10 | ||
| RPF(AA)1.0 | 25 | 2.8 | 2.9 | 2.9 | 2.8 | 2.6 | 2.3 |
| RPF(AA)1.3 | 5.7 | 5.7 | 5.7 | 5.6 | 5.3 | 4.7 | |
| RPF(AA)1.6 | 9.5 | 9.6 | 9.6 | 9.4 | 8.8 | 7.9 | |
| RPF(AA)1.8 | 11.3 | 11.4 | 11.4 | 11.1 | 10.5 | 9.3 | |
| RPF(AA)2.0 | 14.0 | 14.1 | 14.1 | 13.8 | 13.0 | 11.5 | |
| RPF(AA)2.2 | 15.0 | 15.2 | 15.2 | 14.8 | 14.0 | 12.4 | |
| RPF(AA)2.4 | 17.7 | 17.9 | 17.9 | 17.4 | 16.4 | 14.6 | |
| RPF(AA)3.0 | 29.3 | 29.6 | 29.6 | 28.9 | 27.2 | 24.2 | |
| RPF(AA)3.2 | 32.3 | 32.7 | 32.6 | 31.8 | 30.0 | 26.6 | |
| RPF(AB)4.0 | 53.7 | 54.4 | 54.2 | 52.9 | 49.9 | 44.3 | |
| RPF(AB)4.5 | 71.8 | 72.7 | 72.5 | 70.8 | 66.7 | 59.2 | |
| RPF(AA)1.0 | 35 | 2.9 | 2.9 | 3.0 | 2.9 | 2.9 | 2.7 |
| RPF(AA)1.3 | 5.7 | 5.8 | 5.9 | 5.9 | 5.7 | 5.4 | |
| RPF(AA)1.6 | 9.6 | 9.8 | 9.9 | 9.9 | 9.6 | 9.0 | |
| RPF(AA)1.8 | 11.4 | 11.7 | 11.8 | 11.7 | 11.4 | 10.7 | |
| RPF(AA)2.0 | 14.1 | 14.4 | 14.6 | 14.5 | 14.1 | 13.2 | |
| RPF(AA)2.2 | 15.2 | 15.5 | 15.7 | 15.6 | 15.2 | 14.2 | |
| RPF(AA)2.4 | 17.9 | 18.3 | 18.5 | 18.4 | 17.9 | 16.8 | |
| RPF(AA)3.0 | 29.6 | 30.3 | 30.6 | 30.4 | 29.6 | 27.7 | |
| RPF(AA)3.2 | 32.6 | 33.3 | 33.7 | 33.5 | 32.6 | 30.6 | |
| RPF(AB)4.0 | 54.2 | 55.5 | 56.1 | 55.8 | 54.2 | 50.8 | |
| RPF(AB)4.5 | 72.5 | 74.2 | 75.0 | 74.6 | 72.5 | 68.0 | |
| RPF(AA)1.0 | 45 | 2.8 | 2.9 | 2.9 | 3.0 | 2.9 | 2.9 |
| RPF(AA)1.3 | 5.6 | 5.8 | 5.9 | 5.9 | 5.9 | 5.7 | |
| RPF(AA)1.6 | 9.4 | 9.7 | 9.9 | 10.0 | 9.9 | 9.6 | |
| RPF(AA)1.8 | 11.1 | 11.5 | 11.8 | 11.9 | 11.8 | 11.4 | |
| RPF(AA)2.0 | 13.8 | 14.2 | 14.6 | 14.7 | 14.6 | 14.1 | |
| RPF(AA)2.2 | 14.8 | 15.3 | 15.7 | 15.8 | 15.7 | 15.2 | |
| RPF(AA)2.4 | 17.4 | 18.0 | 18.4 | 18.6 | 18.5 | 17.9 | |
| RPF(AA)3.0 | 28.9 | 29.8 | 30.5 | 30.8 | 30.6 | 29.6 | |
| RPF(AA)3.2 | 31.8 | 32.9 | 33.6 | 33.9 | 33.7 | 32.6 | |
| RPF(AB)4.0 | 52.9 | 54.7 | 55.9 | 56.5 | 56.0 | 54.2 | |
| RPF(AB)4.5 | 70.8 | 73.2 | 74.9 | 75.6 | 74.9 | 72.5 | |
| RPF(AA)1.0 | 55 | 2.6 | 2.7 | 2.8 | 2.9 | 2.9 | 2.9 |
| RPF(AA)1.3 | 5.2 | 5.5 | 5.6 | 5.8 | 5.8 | 5.7 | |
| RPF(AA)1.6 | 8.8 | 9.2 | 9.5 | 9.7 | 9.8 | 9.7 | |
| RPF(AA)1.8 | 10.4 | 10.9 | 11.3 | 11.5 | 11.6 | 11.5 | |
| RPF(AA)2.0 | 12.9 | 13.5 | 13.9 | 14.3 | 14.4 | 14.2 | |
| RPF(AA)2.2 | 13.9 | 14.5 | 15.0 | 15.3 | 15.4 | 15.3 | |
| RPF(AA)2.4 | 16.3 | 17.1 | 17.7 | 18.1 | 18.2 | 18.0 | |
| RPF(AA)3.0 | 27.0 | 28.2 | 29.2 | 29.9 | 30.1 | 29.8 | |
| RPF(AA)3.2 | 29.8 | 31.1 | 32.2 | 32.9 | 33.2 | 32.8 | |
| RPF(AB)4.0 | 49.5 | 51.7 | 53.5 | 54.7 | 55.2 | 54.6 | |
| RPF(AB)4.5 | 66.2 | 69.2 | 71.6 | 73.3 | 73.8 | 73.0 | |
Refrigeration Capacity Extension Sheet (R410A)
| Product Model | Condensing Temperature , CT (°C) | Cooling Capacity [kW] Evaporating Temperature [°C] |
|||||
|---|---|---|---|---|---|---|---|
| -40 | -30 | -20 | -10 | 0 | 10 | ||
| RPF(AA)1.0 | 25 | 3.5 | 3.4 | 3.4 | 3.2 | 2.9 | 2.4 |
| RPF(AA)1.3 | 6.9 | 6.9 | 6.7 | 6.4 | 5.8 | 4.8 | |
| RPF(AA)1.6 | 11.6 | 11.6 | 11.3 | 10.7 | 9.7 | 8.1 | |
| RPF(AA)1.8 | 13.8 | 13.8 | 13.4 | 12.7 | 11.6 | 9.6 | |
| RPF(AA)2.0 | 17.1 | 17.0 | 16.6 | 15.8 | 14.3 | 11.8 | |
| RPF(AA)2.2 | 18.4 | 18.3 | 17.8 | 16.9 | 15.4 | 12.7 | |
| RPF(AA)2.4 | 21.6 | 21.5 | 21.0 | 20.0 | 18.1 | 15.0 | |
| RPF(AA)3.0 | 35.8 | 35.6 | 34.8 | 33.0 | 30.0 | 24.8 | |
| RPF(AA)3.2 | 39.5 | 39.3 | 38.3 | 36.4 | 33.0 | 27.3 | |
| RPF(AB)4.0 | 65.6 | 65.3 | 63.8 | 60.6 | 54.9 | 45.5 | |
| RPF(AB)4.5 | 87.8 | 87.4 | 85.3 | 81.0 | 73.5 | 60.8 | |
| RPF(AA)1.0 | 35 | 3.5 | 3.5 | 3.5 | 3.4 | 3.2 | 2.9 |
| RPF(AA)1.3 | 7.0 | 7.0 | 6.9 | 6.8 | 6.4 | 5.8 | |
| RPF(AA)1.6 | 11.7 | 11.8 | 11.7 | 11.4 | 10.7 | 9.7 | |
| RPF(AA)1.8 | 13.9 | 14.0 | 13.9 | 13.5 | 12.8 | 11.5 | |
| RPF(AA)2.0 | 17.2 | 17.3 | 17.2 | 16.7 | 15.8 | 14.2 | |
| RPF(AA)2.2 | 18.5 | 18.6 | 18.4 | 17.9 | 17.0 | 15.3 | |
| RPF(AA)2.4 | 21.8 | 21.9 | 21.7 | 21.1 | 20.0 | 18.0 | |
| RPF(AA)3.0 | 36.0 | 36.3 | 36.0 | 35.0 | 33.1 | 29.8 | |
| RPF(AA)3.2 | 39.7 | 39.9 | 39.6 | 38.5 | 36.4 | 32.8 | |
| RPF(AB)4.0 | 66.0 | 66.5 | 65.9 | 64.1 | 60.6 | 54.6 | |
| RPF(AB)4.5 | 88.3 | 88.9 | 88.2 | 85.8 | 81.1 | 73.1 | |
| RPF(AA)1.0 | 45 | 3.4 | 3.4 | 3.4 | 3.4 | 3.3 | 3.1 |
| RPF(AA)1.3 | 6.7 | 6.8 | 6.9 | 6.8 | 6.6 | 6.2 | |
| RPF(AA)1.6 | 11.3 | 11.5 | 11.5 | 11.4 | 11.1 | 10.4 | |
| RPF(AA)1.8 | 13.4 | 13.6 | 13.7 | 13.5 | 13.1 | 12.3 | |
| RPF(AA)2.0 | 16.6 | 16.9 | 16.9 | 16.8 | 16.2 | 15.3 | |
| RPF(AA)2.2 | 17.8 | 18.1 | 18.2 | 18.0 | 17.4 | 16.4 | |
| RPF(AA)2.4 | 21.0 | 21.4 | 21.5 | 21.2 | 20.6 | 19.3 | |
| RPF(AA)3.0 | 34.7 | 35.3 | 35.5 | 35.1 | 34.0 | 32.0 | |
| RPF(AA)3.2 | 38.3 | 38.9 | 39.1 | 38.7 | 37.5 | 35.2 | |
| RPF(AB)4.0 | 63.7 | 64.8 | 65.1 | 64.4 | 62.4 | 58.6 | |
| RPF(AB)4.5 | 85.2 | 86.6 | 87.1 | 86.1 | 83.4 | 78.4 | |
| RPF(AA)1.0 | 55 | 3.0 | 3.1 | 3.2 | 3.2 | 3.2 | 3.0 |
| RPF(AA)1.3 | 6.1 | 6.3 | 6.4 | 6.4 | 6.3 | 6.1 | |
| RPF(AA)1.6 | 10.3 | 10.5 | 10.7 | 10.8 | 10.6 | 10.2 | |
| RPF(AA)1.8 | 12.2 | 12.5 | 12.7 | 12.8 | 12.6 | 12.1 | |
| RPF(AA)2.0 | 15.0 | 15.5 | 15.7 | 15.8 | 15.6 | 15.0 | |
| RPF(AA)2.2 | 16.2 | 16.6 | 16.9 | 17.0 | 16.7 | 16.1 | |
| RPF(AA)2.4 | 19.1 | 19.6 | 19.9 | 20.0 | 19.7 | 19.0 | |
| RPF(AA)3.0 | 31.5 | 32.4 | 33.0 | 33.1 | 32.6 | 31.5 | |
| RPF(AA)3.2 | 34.7 | 35.7 | 36.3 | 36.5 | 36.0 | 34.7 | |
| RPF(AB)4.0 | 57.8 | 59.4 | 60.4 | 60.6 | 59.8 | 57.7 | |
| RPF(AB)4.5 | 77.3 | 79.5 | 80.9 | 81.1 | 80.0 | 77.2 | |
Refrigeration Capacity Extension Sheet (R32)
| Product Model | Condensing Temperature , CT (°C) | Cooling Capacity [kW] Evaporating Temperature [°C] |
|||||
|---|---|---|---|---|---|---|---|
| -40 | -30 | -20 | -10 | 0 | 10 | ||
| RPF(AA)1.0 | 25 | 5.2 | 5.1 | 4.9 | 4.6 | 4.1 | 3.4 |
| RPF(AA)1.3 | 10.3 | 10.2 | 9.8 | 9.2 | 8.3 | 6.8 | |
| RPF(AA)1.6 | 17.4 | 17.1 | 16.5 | 15.5 | 13.9 | 11.4 | |
| RPF(AA)1.8 | 20.6 | 20.3 | 19.6 | 18.4 | 16.5 | 13.5 | |
| RPF(AA)2.0 | 25.5 | 25.1 | 24.2 | 22.8 | 20.4 | 16.7 | |
| RPF(AA)2.2 | 27.4 | 27.0 | 26.1 | 24.5 | 22.0 | 18.0 | |
| RPF(AA)2.4 | 32.3 | 31.8 | 30.7 | 28.8 | 25.9 | 21.2 | |
| RPF(AA)3.0 | 53.5 | 52.6 | 50.8 | 47.7 | 42.8 | 35.1 | |
| RPF(AA)3.2 | 58.9 | 58.0 | 56.0 | 52.6 | 47.2 | 38.7 | |
| RPF(AB)4.0 | 98.0 | 96.4 | 93.1 | 87.5 | 78.5 | 64.3 | |
| RPF(AB)4.5 | 131.1 | 129.0 | 124.6 | 117.0 | 105.0 | 86.1 | |
| RPF(AA)1.0 | 35 | 5.4 | 5.3 | 5.2 | 5.0 | 4.7 | 4.2 |
| RPF(AA)1.3 | 10.7 | 10.7 | 10.5 | 10.0 | 9.4 | 8.4 | |
| RPF(AA)1.6 | 18.1 | 18.0 | 17.6 | 16.9 | 15.8 | 14.1 | |
| RPF(AA)1.8 | 21.5 | 21.3 | 20.9 | 20.1 | 18.7 | 16.7 | |
| RPF(AA)2.0 | 26.5 | 26.4 | 25.8 | 24.8 | 23.2 | 20.7 | |
| RPF(AA)2.2 | 28.5 | 28.3 | 27.8 | 26.7 | 24.9 | 22.2 | |
| RPF(AA)2.4 | 33.6 | 33.4 | 32.7 | 31.4 | 29.4 | 26.2 | |
| RPF(AA)3.0 | 55.6 | 55.3 | 54.1 | 52.0 | 48.6 | 43.3 | |
| RPF(AA)3.2 | 61.3 | 60.9 | 59.7 | 57.3 | 53.5 | 47.7 | |
| RPF(AB)4.0 | 102.0 | 101.3 | 99.2 | 95.4 | 89.1 | 79.4 | |
| RPF(AB)4.5 | 136.4 | 135.5 | 132.8 | 127.6 | 119.2 | 106.3 | |
| RPF(AA)1.0 | 45 | 5.4 | 5.4 | 5.4 | 5.2 | 5.0 | 4.7 |
| RPF(AA)1.3 | 10.9 | 10.9 | 10.8 | 10.5 | 10.0 | 9.3 | |
| RPF(AA)1.6 | 18.3 | 18.3 | 18.1 | 17.7 | 16.9 | 15.7 | |
| RPF(AA)1.8 | 21.7 | 21.7 | 21.5 | 21.0 | 20.0 | 18.6 | |
| RPF(AA)2.0 | 26.8 | 26.9 | 26.6 | 25.9 | 24.8 | 23.0 | |
| RPF(AA)2.2 | 28.8 | 28.9 | 28.6 | 27.9 | 26.6 | 24.7 | |
| RPF(AA)2.4 | 34.0 | 34.0 | 33.7 | 32.8 | 31.4 | 29.1 | |
| RPF(AA)3.0 | 56.2 | 56.3 | 55.7 | 54.3 | 51.9 | 48.2 | |
| RPF(AA)3.2 | 62.0 | 62.0 | 61.4 | 59.9 | 57.2 | 53.1 | |
| RPF(AB)4.0 | 103.1 | 103.1 | 102.1 | 99.6 | 95.2 | 88.4 | |
| RPF(AB)4.5 | 137.9 | 138.0 | 136.6 | 133.2 | 127.4 | 118.2 | |
| RPF(AA)1.0 | 55 | 5.3 | 5.3 | 5.3 | 5.2 | 5.1 | 4.8 |
| RPF(AA)1.3 | 10.6 | 10.7 | 10.6 | 10.5 | 10.2 | 9.7 | |
| RPF(AA)1.6 | 17.8 | 17.9 | 17.9 | 17.7 | 17.1 | 16.3 | |
| RPF(AA)1.8 | 21.1 | 21.3 | 21.2 | 21.0 | 20.3 | 19.3 | |
| RPF(AA)2.0 | 26.2 | 26.3 | 26.3 | 25.9 | 25.2 | 23.9 | |
| RPF(AA)2.2 | 28.1 | 28.3 | 28.2 | 27.9 | 27.0 | 25.7 | |
| RPF(AA)2.4 | 33.1 | 33.4 | 33.3 | 32.8 | 31.9 | 30.3 | |
| RPF(AA)3.0 | 54.8 | 55.2 | 55.1 | 54.3 | 52.7 | 50.1 | |
| RPF(AA)3.2 | 60.4 | 60.8 | 60.7 | 59.8 | 58.1 | 55.2 | |
| RPF(AB)4.0 | 100.5 | 101.2 | 101.0 | 99.5 | 96.6 | 91.8 | |
| RPF(AB)4.5 | 134.4 | 135.4 | 135.1 | 133.2 | 129.3 | 122.9 | |
Refrigeration Capacity Extension Sheet (R134A)
| Product Model | Condensing Temperature , CT (°C) | Cooling Capacity [kW] Evaporating Temperature [°C] |
|||||
|---|---|---|---|---|---|---|---|
| -40 | -30 | -20 | -10 | 0 | 10 | ||
| RPF(AA)1.0 | 25 | 2.0 | 2.0 | 2.0 | 2.0 | 1.8 | 1.6 |
| RPF(AA)1.3 | 4.0 | 4.1 | 4.1 | 4.0 | 3.7 | 3.1 | |
| RPF(AA)1.6 | 6.8 | 6.9 | 6.9 | 6.7 | 6.2 | 5.3 | |
| RPF(AA)1.8 | 8.0 | 8.1 | 8.1 | 7.9 | 7.3 | 6.2 | |
| RPF(AA)2.0 | 9.9 | 10.1 | 10.1 | 9.8 | 9.1 | 7.7 | |
| RPF(AA)2.2 | 10.7 | 10.8 | 10.8 | 10.5 | 9.8 | 8.3 | |
| RPF(AA)2.4 | 12.6 | 12.8 | 12.7 | 12.4 | 11.5 | 9.8 | |
| RPF(AA)3.0 | 20.8 | 21.1 | 21.1 | 20.5 | 19.0 | 16.2 | |
| RPF(AA)3.2 | 22.9 | 23.3 | 23.2 | 22.6 | 21.0 | 17.8 | |
| RPF(AB)4.0 | 38.1 | 38.7 | 38.6 | 37.5 | 34.9 | 29.6 | |
| RPF(AB)4.5 | 50.9 | 51.8 | 51.7 | 50.2 | 46.7 | 39.6 | |
| RPF(AA)1.0 | 35 | 2.1 | 2.1 | 2.2 | 2.1 | 2.1 | 1.9 |
| RPF(AA)1.3 | 4.1 | 4.2 | 4.3 | 4.3 | 4.2 | 3.9 | |
| RPF(AA)1.6 | 6.9 | 7.1 | 7.3 | 7.2 | 7.0 | 6.5 | |
| RPF(AA)1.8 | 8.2 | 8.5 | 8.6 | 8.6 | 8.3 | 7.7 | |
| RPF(AA)2.0 | 10.2 | 10.5 | 10.7 | 10.6 | 10.3 | 9.5 | |
| RPF(AA)2.2 | 11.0 | 11.3 | 11.5 | 11.4 | 11.1 | 10.2 | |
| RPF(AA)2.4 | 12.9 | 13.3 | 13.5 | 13.4 | 13.0 | 12.1 | |
| RPF(AA)3.0 | 21.4 | 22.0 | 22.3 | 22.2 | 21.6 | 20.0 | |
| RPF(AA)3.2 | 23.5 | 24.2 | 24.6 | 24.5 | 23.7 | 22.0 | |
| RPF(AB)4.0 | 39.2 | 40.3 | 40.9 | 40.8 | 39.5 | 36.6 | |
| RPF(AB)4.5 | 52.4 | 53.9 | 54.8 | 54.6 | 52.9 | 48.9 | |
| RPF(AA)1.0 | 45 | 2.1 | 2.1 | 2.2 | 2.2 | 2.2 | 2.1 |
| RPF(AA)1.3 | 4.1 | 4.3 | 4.4 | 4.5 | 4.4 | 4.3 | |
| RPF(AA)1.6 | 6.9 | 7.2 | 7.4 | 7.5 | 7.5 | 7.2 | |
| RPF(AA)1.8 | 8.2 | 8.5 | 8.8 | 8.9 | 8.9 | 8.6 | |
| RPF(AA)2.0 | 10.1 | 10.6 | 10.9 | 11.0 | 11.0 | 10.6 | |
| RPF(AA)2.2 | 10.9 | 11.4 | 11.7 | 11.9 | 11.8 | 11.4 | |
| RPF(AA)2.4 | 12.9 | 13.4 | 13.8 | 14.0 | 13.9 | 13.4 | |
| RPF(AA)3.0 | 21.3 | 22.1 | 22.8 | 23.1 | 23.0 | 22.2 | |
| RPF(AA)3.2 | 23.4 | 24.4 | 25.1 | 25.5 | 25.4 | 24.5 | |
| RPF(AB)4.0 | 39.0 | 40.6 | 41.8 | 42.4 | 42.2 | 40.8 | |
| RPF(AB)4.5 | 52.2 | 54.3 | 55.9 | 56.7 | 56.4 | 54.5 | |
| RPF(AA)1.0 | 55 | 2.0 | 2.1 | 2.2 | 2.2 | 2.3 | 2.2 |
| RPF(AA)1.3 | 3.9 | 4.1 | 4.3 | 4.5 | 4.5 | 4.5 | |
| RPF(AA)1.6 | 6.6 | 7.0 | 7.3 | 7.5 | 7.6 | 7.6 | |
| RPF(AA)1.8 | 7.9 | 8.3 | 8.7 | 8.9 | 9.0 | 9.0 | |
| RPF(AA)2.0 | 9.7 | 10.3 | 10.7 | 11.0 | 11.2 | 11.1 | |
| RPF(AA)2.2 | 10.5 | 11.0 | 11.5 | 11.8 | 12.0 | 11.9 | |
| RPF(AA)2.4 | 12.3 | 13.0 | 13.6 | 14.0 | 14.2 | 14.1 | |
| RPF(AA)3.0 | 20.4 | 21.5 | 22.4 | 23.1 | 23.4 | 23.3 | |
| RPF(AA)3.2 | 22.5 | 23.7 | 24.7 | 25.5 | 25.8 | 25.6 | |
| RPF(AB)4.0 | 37.4 | 39.4 | 41.1 | 42.3 | 42.9 | 42.7 | |
| RPF(AB)4.5 | 50.0 | 52.7 | 55.0 | 56.7 | 57.5 | 57.1 | |
| Coil Model | Suitable Valve Body Series | Size (mm) | Insulation Sleeve | |||
|---|---|---|---|---|---|---|
| Φ A | B | C | D | |||
| RBAA1200013 | RPF(AA)1.0~3.2 RPF(AB)4.0~4.5 |
37.5 | 27.9 | 600 | 700 | XHP-5 |
| RBAA1200004 | RPF(AA)1.0~3.2 RPF(AB)4.0~4.5 |
37.5 | 27.9 | 900 | 1000 | XHP-5 |
| RBAA1200007 | RPF(AA)1.0~3.2 RPF(AB)4.0~4.5 |
37.5 | 27.9 | 1400 | 1500 | XHP-5 |
| RBAA1200002 | RPF(AA)1.0~3.2 RPF(AB)4.0~6.5 |
37.5 | 27.9 | 1900 | 2000 | XHP-5 |
| Body Series | Suitable Valve Body Series | Size (mm) | ||||
|---|---|---|---|---|---|---|
| E | G | F | ΦH | ΦN | ||
| RPF(AA) 1.0~2.4 | RBAA | 80 | 36 | 30 | 6.35 | 17.35 |
| RPF(AA)3.0~3.2 | RBAA | 83 | 39 | 39 | 7.94 | 17.35 |
| RPF(AB)4.0~4.5 | RBAA | 101 | 47 | 51 | 9.52 | 17.35 |
| RPF(AB)5.5~6.5 | RBAA | 113 | 61 | 53 | 12.7 | 17.35 |